Cabinet Heater and Controller




HGL 046 250W-400W Fan Heater
Product Description
· Compact design
· Clip fixing
· Long service life
· Maintenance free
· Temperature safety cut-out
Compact fan heater prevents formation of condensation. The integrated high performanceaxial fan provides forced air circulation and SO guarantees an even temperature in enclosureswith internal terminal connector.
Technical Data | |
Heating element | Resistance heater |
Temperature safety cut-out | To protect against overheating in case of fan failure |
Heater body | Anodised extruded aluminium profile |
Surface temperature | Max. 75℃ ( 400W ) |
Axial fan, ball bearing | Airflow, free flow |
AC: 45m3/h ( 50HZ ) or 54m3/h ( 60HZ ), DC:54m3/h | |
DC: 54m3/h | |
Service life 50 000h at 25℃ ( 77℉ ) | |
Connection | Internal connection terminal 1.5mm2 with clamping torque 0.8Nm max. |
Connection casing | Plastice according to UL94 V-0, black |
Mounting | clip for 35mm DIN rall, EN 60715mmDIN |
Fitting position | Vertical |
Operating / Storage temperature | -45 to+70℃ ( -49 to+158℉ ) |
Protection type / Protection class | IP20, I ( earthed ) |
Note: In the case of 24VDC and 48VDC the fan heater has to be switched via a relay. For this purpose we recommend our electronic relay SM 010 ( Art. No. 01000.0-00 and 01001.0-00 ).
Drawing
Connection diagram
Art. No | Operating votage | Heating capacity | Length(L) | Weight (approx.) |
04640.0-00 | 230VAC, 50/60HZ | 250W | 128mm | 1.10kg |
04641.0-00 | 230VAC, 50/60HZ | 400W | 222mm | 1.40kg |
04640.9-00 | 120VAC, 50/60HZ | 250W | 182mm | 1.10kg |
04641.9-00 | 120VAC, 50/60HZ | 400W | 222mm | 1.40kg |
04640.1-00 | 24VDC | 250W | 182mm | 1.10kg |
04640.2-00 | 48VDC | 250W | 182mm | 1.10kg |
04641.2-00 | 48VDC | 400W | 222mm | 1.40kg |