Product Search
Keyword:
    Product List      
   Mini Circuit Breaker
   Earth Leakage Circuit Breaker
   Moulded Case Circuit Breaker
   AC Contactor
   Relay
   Fuse
   Meter
  Switch
   Tool
   Lighting
   Stabilizer
   Distribution Box
   Wire Accessories
   Industrial Plug-Socket
   Wire-Cable
   Pushbutton And Indicator
 
Products Home_Current Location_Products
Changeover Switch FW26 series

 




















Application

    FW26 series changeover switch is used in the circuits of AC 50Hz,rated voltage up to 690V, DC voltage up to 240V, rated current up to 100A, to not frequently switch on/off circuit, transfer and control circuits,also it can directly control small capacity motor or be used for master control or electric meters. The switch is used widely in circuit control, test equipment, switch for motor, master control, welding machine and etc.
Advantages: small size, multifunction, compact structure, high quality material, good in sul­ation, agile operation, reliability, safety, good appearance.
FVV26-20, FW26-25, FVV26-32, FVV26-63, provide function of finger protection.

 

Specifications

Model

FW26-10

FW26-20

FW26-25

Rated Insulation Voltage Ui (V)

690V

Rated Thermal Current Lth (A)

10

20

25

Rated Operating Voltage Ue (V)

220

380

500

220

380

500

220

380

500

AC-21A AC-22A(A)

10

20

20

AC-2 3P (KW)

2

3.5

7

4

7.5

10

5.5

11

13

AC-3 3p/1 P (KW)

1/0.5

3.5/1

2.5

3/2.2

5.5/3

5.5

4/3

7.5/3.7

7.5

AC-4 3P/1 P (KW)

0.25/0.35

1/1.5

1

0.55/0.75

1.5/1.5

1.5

1.5/1.1

3/2.2

2.2

AC-23 3P/1P (KW)

2.5/1

3.5/2

4.5

3.7/2.5

7.5/3.7

7.5

5.5/3

11/5.5

11

AC-15 (A)

3

2

-

5

4

-

8

5

 

DC-13 (A)

 

 

 

1

 

 

 

 

 

Mechanical Life

60X104 ops, operation frequency:120ops/hour

Electrical Life AC-15

20X104 ops, operation frequency:300ops/hour

Electrical Life at DC-13

6X104 ops, operation frequency:300ops/hour

 

Model

FW26-32

FW26-63

FW26-125

FW26-160

Rated insulation voltage Ui (V)

690V

Rated thermal current Ith (A)

32

63

125

160

Rated operating voltage Ue (V)

220

380

500

220

380

500

220

380

220

380

AC-21A AC-22A(A)

32

63

125

160

AC-2 3P (KW)

7.5

15

18.5

18.5

30

40

30

45

37

55

AC-3 3P/1P (KW)

5.5/4

11/5.5

11

11/6

18.5/11

18.5

15/7.5

30/13

22/11

37/18.5

AC-4 3P/1 P (KW)

2.5/1.5

5.5/3

5.5

5.5/2.4

7.5/4

7.5

6/3

11/5.5

10/4

15/7.5

AC-23 3P/1P (KW)

7.5/4

15/7.5

15

15/10

30/18.5

45

30/15

45/22

37/22

75/37

AC-15 (A)

14

6

 

-

 

 

 

 

 

 

DC-13 (A)

1.5

 

11

 

Mechanical life

60X104 ops, operation frequency:120ops/hour

Electrical life AC-15

20X104 ops, operation frequency:300ops/hour

Electrical life at DC-13

6X104 ops, operation frequency 300ops/hour

 

Dimensions

 


 


Published:2013-9-29   【Print this page】 【Close the window】【products】  Browse:298 Secondary

 

 

Copyright@[2013] YUEQING CITY ESNEW ELECTRIC CO., LTD. http://www.esnew.com sales@esnew.com